| Model No. | PMH7500 | PMH10000A | PMH10000B | |
|---|---|---|---|---|
| Ratings | 7.5 KVA | 10 KVA | 10 KVA | |
| Inverter Switching Element | IGBT | |||
| Inverter Charger Topology | IGBT Based Buck Type | |||
| Controller | 16-Bit dsPIC | |||
| Nominal DC | 120V | 120V | 180V | |
| Inverter Parameters | ||||
| Output Voltage | 230V ± 1% , 1ɸ | |||
| Maximum Output Current | 25A | 33A | 33A | |
| Output Frequency | 50Hz ± 1 | |||
| Isolation Transformer | Provided Inbuilt | |||
| Crest Factor | 3:1 | |||
| Output Waveform | Pure Sinusoidal | |||
| THD | Linear Load | < 3% | ||
| Non Linear Load | < 5% | |||
| Overload | 110% for 10 minutes, 125% for 1 minute, 150% for 10 sec | |||
| Inverter Efficiency | > 85% | |||
| Protections & Alarm | Over and Under Voltage Grid, Over Load, Battery Low &High , Short Circuit, Over Temperature | |||
| Remote Monitoring Port RS232/RS485 (Modbus) | Optional | |||
| Grid Input Parameters | ||||
| Nominal Grid Voltage | 230V, 1ɸ | |||
| Nominal Grid Frequency | 50Hz | |||
| Input Low Cut Voltage | 160V ± 5V | 180V ± 5V | ||
| Input Low Recovery Voltage | > 170V ± 5V | > 190 ± 5V | ||
| Input High Cut Voltage | 280V ± 5V | |||
| Input High Recovery Voltage | < 270V ± 5V | |||
| Input Frequency Range | 47Hz - 53Hz | |||
| Battery Parameters | ||||
| Battery Charging | Grid | 15A ± 1A (Please consider derating factor also) | ||
| Boost Voltage | Grid | 145V ± 1V | 145V ± 1V | 217V ± 2V |
| Float Voltage | Grid | 135V ± 1V | 135V ± 1V | 202V ± 2V |
| Equalization Voltage | Grid | 155V ± 1V | 155V ± 1V | 232V ± 2V |
| Battery Low Buzzer | 107V ± 1V | 107V ± 1V | 160V ± 2V | |
| Battery Low Cut | 105V ± 1V | 105V ± 1V | 157V ± 2V | |
| Battery Low Reconnect | 118V ± 1V | 118V ± 1V | 177V ± 2V | |
| Battery High | 170V ± 1V | 170V ± 1V | 255V ± 2V | |
| Display Parameters | LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current | |||
| Display Alarms | Output load Percentage, Overload time, Mains - On / Fail / High / Low , DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Load, Temperature | |||
| Switchgear | Grid MCB, Battery MCB, Load MCB, Manual Rotary Switch | |||
| Enclosure | IP 20 | |||
| Operating Temp. | 0 to 40 Deg C | |||
| Humidity | Upto 95% Rh (non-condensing) | |||
| Cooling | Forced Air | |||
| Noise | < 55 dB, distance 1 meter | |||
| Dimensions in mm (L X W X H) | 700 X 350 X 570 | |||
| Weight(Approx Kgs) | 75 Kg | 90 Kg | ||
| Bypass Switch | Manual Rotary Switch | |||
| Wheels | Provided | |||