Model No. PMH7500 PMH10000A PMH10000B
Ratings 7.5 KVA 10 KVA 10 KVA
Inverter Switching Element IGBT
Inverter Charger Topology IGBT Based Buck Type
Controller 16-Bit dsPIC
Nominal DC 120V 120V 180V
Inverter Parameters
Output Voltage 230V ± 1% , 1ɸ
Maximum Output Current 25A 33A 33A
Output Frequency 50Hz ± 1
Isolation Transformer Provided Inbuilt
Crest Factor 3:1
Output Waveform Pure Sinusoidal
THD Linear Load < 3%
Non Linear Load < 5%
Overload 110% for 10 minutes, 125% for 1 minute, 150% for 10 sec
Inverter Efficiency > 85%
Protections & Alarm Over and Under Voltage Grid, Over Load, Battery Low &High , Short Circuit, Over Temperature
Remote Monitoring Port RS232/RS485 (Modbus) Optional
Grid Input Parameters
Nominal Grid Voltage 230V, 1ɸ
Nominal Grid Frequency 50Hz
Input Low Cut Voltage 160V ± 5V 180V ± 5V
Input Low Recovery Voltage > 170V ± 5V > 190 ± 5V
Input High Cut Voltage 280V ± 5V
Input High Recovery Voltage < 270V ± 5V
Input Frequency Range 47Hz - 53Hz
Battery Parameters
Battery Charging Grid 15A ± 1A (Please consider derating factor also)
Boost Voltage Grid 145V ± 1V 145V ± 1V 217V ± 2V
Float Voltage Grid 135V ± 1V 135V ± 1V 202V ± 2V
Equalization Voltage Grid 155V ± 1V 155V ± 1V 232V ± 2V
Battery Low Buzzer 107V ± 1V 107V ± 1V 160V ± 2V
Battery Low Cut 105V ± 1V 105V ± 1V 157V ± 2V
Battery Low Reconnect 118V ± 1V 118V ± 1V 177V ± 2V
Battery High 170V ± 1V 170V ± 1V 255V ± 2V
Display Parameters LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current
Display Alarms Output load Percentage, Overload time, Mains - On / Fail / High / Low , DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Load, Temperature
Switchgear Grid MCB, Battery MCB, Load MCB, Manual Rotary Switch
Enclosure IP 20
Operating Temp. 0 to 40 Deg C
Humidity Upto 95% Rh (non-condensing)
Cooling Forced Air
Noise < 55 dB, distance 1 meter
Dimensions in mm (L X W X H) 700 X 350 X 570
Weight(Approx Kgs) 75 Kg 90 Kg
Bypass Switch Manual Rotary Switch
Wheels Provided

Our Satisfied Clients

some of our great clients and their review

SunGarner deploys world-class technology to design, install and commission benchmark solar projects. We avail their services including design, engineering & implementation of solar Off Grid and On Grid Power Plants. It has been more than 5 years now and they are delivering with the latest technology.

#

Mr. Sunil Sharma Group Vice President, Modi Xerox

SunGarner has a dynamic in-house R&D Department with an experienced back-up, providing customized solutions on problems pertaining to the energy needs of a wide variety of Industrial, Commercial and Residential establishments in several areas. I am happy with their after-sales service too.

#

Mr. Vinod Ajitsaria Managing Director, V N Dyers & Textiles

#
#
#
#
#
#
#
#
#
#